Re: fence_apc

[Date Prev][Date Next][Thread Prev][Thread Next][Date Index][Thread Index]

 



My 7920 came with a book about their new CLI. It's invoked weird with " -c" appended to the password but after that it looks very sane and easy to use. With no menu and a stated purpose of making it easier to use from a script, it may be worth looking at.

   scottb

Robert Clark wrote:
On Mon, 2007-11-19 at 11:20 -0500, jim parsons wrote:
I'm pretty sure this is coming about because of something around line
664 which is expecting "Outlet Control" to be option number 3 while it's
actually option number 2. The problem is that you can't rely on the
option number even for a known firmware version as the number of options
in that menu will change depending on other factors (like whether you
are logged in to the switch as an administrative user or not).

  Ante Karamatić is ending up in a different menu (Phase Monitor), but I
guess it's essentially the same problem.


--
Linux-cluster mailing list
Linux-cluster@xxxxxxxxxx
https://www.redhat.com/mailman/listinfo/linux-cluster

[Index of Archives]     [Corosync Cluster Engine]     [GFS]     [Linux Virtualization]     [Centos Virtualization]     [Centos]     [Linux RAID]     [Fedora Users]     [Fedora SELinux]     [Big List of Linux Books]     [Yosemite Camping]