Re: fence_apc

[Date Prev][Date Next][Thread Prev][Thread Next][Date Index][Thread Index]

 



On Sun, 2007-11-18 at 16:37 +0100, Ante Karamatić wrote:

> When I run 'fence_node node2', I get:

[...]

> fence_apc ends up in Phase Monitor, instead of Outlet Control. It
> opens connection to Control console, then enters Device Manager, and
> then instead of entering Outlet Control (2), it enters Phase Monitor
> (1).
> 
> It's an APC AP7920 with firmware v2.7.3. It's an RHCS v2.20070823, from
> Ubuntu 7.10.

  You are not alone! Have a look at:

    https://bugzilla.redhat.com/show_bug.cgi?id=241217

I'm using an AP7920 with v2.7.3 also.

  Since this is a regression, one way around it is to use the older
fence-1.32.25-1 instead. This version used a regular expression to
identify the correct menu option which was more robust against menu
order changes.

	Robert

--
Linux-cluster mailing list
Linux-cluster@xxxxxxxxxx
https://www.redhat.com/mailman/listinfo/linux-cluster