Re: [OT] ups advice

[Date Prev][Date Next][Thread Prev][Thread Next][Date Index][Thread Index]



On 04/15/11 4:38 AM, Howard Fleming wrote:
> I have used several Best Ferrups UPSs over the years, other than one
> that toasted it's transformer, have never had any trouble out of them
> (just replace the battery every 3 to 4 years....).
>
> They are picky about their input power, do not run not connect them to
> an auto regulating transformer (not the proper term?), or on the output
> of other UPSs, it can cause interesting problems...

I don't think they make any FerrUPS anymore.  Those were based on a 
massive ferroresonant transformer which, yes, is very sensitive to the 
input frequency.  Specifically, they don't like generator power, unless 
it has extremely well regulated frequency output (such as a DC generator 
with a digital sinusoidal converter)